These translations are machine translations from Google. SOEW makes these available for your convenience, but cannot be held responsible for the accuracy of any content lost through translation Bookmark increase font size default font size decrease font size e-mail this page print this page

specifications

Flex Power

Description

Plain annealed flexible copper conductor, flexible PVC bedded, with a Nitrite PVC sheath.

Application

For the wiring of:

Control panels and power installations where a flexible conductor is required.

Specification SANS 1507/2002
Voltage Rating   600/1000 V
Temperature Range   -10°C to 70°C
Sheath colours   Black, red, green/yellow, blue
other colours available on request
Technical Information
CABLE SIZE NOMINAL
STRANDING
No.x DIAMETER
APPROX.
OVERALL
DIAMETER
CURRENT
RATING
Note 1
VOLT DROP APPROX. CABLE
WEIGHT
MASS PER
100M COIL
(mm2)   (mm) (A) (MV/A/M) (kg)
        (note 1) (note 1)
25.0 329w x 0.3 11.1 114 0.78 29.4
35.0 455w x 0.3 12.4 141 0.554 38.7
50.0 670w x 0.3 14.8 182 0.386 55.7
70.0 904w x 0.3 16.6 234 0.272 73.6
95.0 1190w x 0.3 19.1 284 0.206 95.3
120.0 550w x 0.5 21.4 330 0.161 131.0

Note 1: Based on a max ambient temperature of 30°C and a max conductor temperature of 70°C

Packaging

Packaging            100 metre
Shrink-wrapped coils

Also available on  500 metre
Wooden drums