These translations are machine translations from Google. SOEW makes these available for your convenience, but cannot be held responsible for the accuracy of any content lost through translation Bookmark increase font size default font size decrease font size e-mail this page print this page

specifications

Single Core Double PVC Cable

Description

Plain annealed stranded copper conductors; insulated with a general purpose grade PVC, unarmoured, PVC Sheath

Application

Power Distribution

Distribution Panels and Transformers

Specification SANS 1507/2002
Voltage Rating   600/1000 V
Temperature Range   -10°C to 70°C
Colour Option   Black (other colours available on request)
Technical Information
CABLE SIZE NOMINAL
STRANDING
No.x DIAMETER
APPROX.
OVERALL
DIAMETER
CURRENT
RATING
Note 1
VOLT DROP

Note 1
APPROX. CABLE
WEIGHT
MASS PER
100M COIL
(mm2)   (mm) (A) (MV/A/M) (kg)
120.0 37 x 2.03 20.2 330 0.41 129
150.0 37 x 2.25 22.3 381 0.34 158
185.0 37 x 2.52 24.7 436 0.29 197
240.0 61 x 2.25 27.8 515 0.25 256
300.0 61 x 2.52 30.9 594 0.22 322
400.0 61 x 2.80 34.4 694 0.20 407
500.0 61 x 3.20 38.3 792 0.185 516
630.0 91 x 2.97 42.5 904 0.175 655

Note 1: These ratings are for 2 cables single phase AC or DC clipped direct as per SANS 0142 table 6.2

Packaging

Packaging            500 metre
Wooden drums